DATACOOL-PACKAGE

Packaged Precision Air Conditioner with built-in fresh air free cooling is a technologically advanced range of P-CRAC units, combining fresh air free cooling and refrigeration to offer maximum value for critical environment consumers, reducing installation expenditure and minimizing energy consumption and operation costs.

Energy Saving

  • Integrated with free cooling system, saving up to 90% of the energy requirements
  • EC supply fan
  • Auto-control optimizes system performance

 

Good structure design and easy maintenance

  • All routine maintenance is from the front of the unit, with easily removable access panels.
  • Offer two structure types for option: packaged and segmental structure. The unit is supplied in sections for on-site assembly, making transport and installation easier.

Reliable Operation

Relibable performance guaranteed by functions and protections designed for the unit.

  • 4 Levels of Password Protection
  • High torque and low leakage air damper is equipped with a high torque actuator to assure the reliability and low leakage. The on/off cycle is less than 90 seconds.
  • Automatic maintenance test
  • Auto-sequencing: equalize runtime of all units

 

Fully automatic control

  • The unit is equipped with a full automatic control system, with auto restart.
  • The unit automatically selects the working mode: mechanic cooling or free cooling according to the outdoor and indoor temperatures. In the event of failure of the refrigeration system, the unit will revert to fresh air cooling mode.
  • All the components connected to microprocessor are continuously tested. In case of malfunction, the failure is shown on the display with information accordingly.

 

Safety Operation

Highly safety performance guaranteed by functions and protections designed for the unit. 

  • 4 Levels of Password Protection
  • Air filter protection device has been developed to maximize the filter working life and enable free cooling to function in harsh environments

 

Certification

Highly safety performance is guranteed by meeting the following standards: 

  • CE

Specification

Unit Model15.UP.E1A115.DN.E1A122.DN.E1A230.DN.E2A245.DN.E2A3.0245.DN.E2A3.03
PerformanceAir Supply

UP/DN

Cooling CapacityTotal Cooling CapacitykW

16.7 

16.7 

23.9 

32.3 

46.3 

46.3 

Sensible Cooling CapacitykW

15.2 

15.2 

22.2 

30.0 

43.3 

43.3 

Free Cooling CapacityCooling CapacitykW

16.7 

16.7 

24.6 

33.0 

48.6 

48.6 

CompressorType 

Hermetic Scroll

PowerkW

4.5

4.5

6.2

9

12.2

12.2

CurrentA

8.1

8.1

12

16.2

22.1

22.1

Over load currentA

11

11

16.4

22

32.8

32.8

Circuit breakerA

11

11

16.4

22

32.8

32.8

Supply FanType 

EC Centrifugal Fan

Fans Quantityn.

1

1

1

1

2

2

Air Volumem3/h

4650

4650

6830

9150

13500

13500

Extra Air PressurePa

0~150Pa(Adjustment)

PowerkW

0.7

0.7

1.3

1.6

2.6

2.6

CurrentA

1.2

1.2

2.1

2.6

4.4

4.4

Over load currentA

1.7

1.7

4

4

8

8

Circuit breakerA

1.7

1.7

4

4

8

8

Power SupplyPower 

400V/3Ph/50Hz

Unit Operating PowerkW

6.1

6.1

9.1

12.4

17.7

17.7

Unit Operating CurrentA

10.8

10.8

16.9

21.9

31.1

31.1

Refrigerant  

R407c

Electric HeaterHeat SupplykW

6

6

6

6

9

9

CurrentA

8.9

8.9

8.9

8.9

15

15

Working Moden.

2

2

2

2

2

2

Unit Operating CurrentA

9.6

9.6

9.6

9.6

16.2

16.2

Condenser FanType 

EC Centrifugal Fan

Fans Quantityn.

1

1

2

2

2

2

Air Volumem3/h

5860

5860

8460

11500

18300

18300

PowerkW

0.9

0.9

1.6

1.8

2.9

2.9

CurrentA

1.5

1.5

2.8

3.1

4.6

4.6

Air FilterQuantity(G2)n.

2

2

4

4

4

4

Quantity(F6)n.

1

1

2

2

2

2

Unit Dimension and WeightWidthmm

1200

1200

1450

1450

2050

2050

Depthmm

1075

1075

1075

1075

1225

1225

Up Section Heightmm

985

860

1010

1010

1170

1170

Middle Section Heightmm

/

/

/

/

/

1620

Down Section Heightmm

1780

1930

2030

2030

2100

550

Total Heightmm

2745

2770

3020

3020

3250

3300

Weightkg

765

765

830

890

1200

1200